Toshiba GR200 Series - (iii)-2 Output signal to BO; (iv) Receiving “Operate command P1-control” from the local-end; (iv)-1 Input signal generated at the local-end

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 940 -
logic programmed by the user in place of the logic shown in Figure 4.9-26. The
user-programmed logic is connected internally to the “operate completed” signal,
hence this signal is now generated by the user-programmed logic at connection
point#2 “User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.9-31, can issue an Operate” signal at the output-point
“TPOS01_P3EX_BO”, when the TPOS01 function determines that the input signal Remote-
P3-Control is true.
(iv) Receiving “Operate command P1-control” from the local-end
Figure 4.9-32 depicts the operation logic of the operate command P1-control from the local-
end.
Signal reception from the
front panel
P1 control from the local-end
Do nothing
Operation
decision
Success
Failed
Operate logic
P1 control from the remote-end
P2 control from the remote-end
P3 control from the remote end
P2 control from the local-end
P1 control by the PLC function
P3 control from the local-end
P2 control by the PLC function
Wait for a command
P1 control from the local-end
P3 control by the PLC function
Select logics
Signal output
P3 control from the remote end
P2 control from the local-end
P1 control from the remote-end
P2 control from the remote-end
P3 control from the local-end
P1 control by the PLC function
P2 control by the PLC function
P3 control by the PLC function
Wait for a next command
Figure 4.9-32 Outline of Operate command ‘P1-control’
Input signal generated at the local-end
Figure 4.9-33 illustrates the operate logic when an Operate command P1 (Local-P1-Control)
signal is applied to the TPOS01 function. The signal is provided when P1-control is keyed on
the IED front panel.