EasyManua.ls Logo

Toshiba GR200 Series - Page 964

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 941 -
TPOS01 function (Function ID: 513001)
Assign to BOs
Operate Cmd.
with ILK condition
S
R
0.1 50.0 s
[TPOS01-CPW]
Operate Cmd.
without ILK condition
Operate condition
[TPOS01-LGCTRCON]
Fixedlogic
Fixedlogic
[TPOS01-LGP1EXOT]
DEV01_CONTROL_REQ
Command Local-P1-Control
513001_7004016D08
TPOS01IN_TMP_28
513001 810401EE57
User configurable condition (PLC#3 connection point)
TPOS01_P1EC_OK_CSF
(513001 8004011E7E)
&
&
1
&
1
1
&
&
&
TPOS01_P1EX_BO
(5130018104011DD0) §§
Input
Output
Operate logic in TPOS01
PLC#3
To BO connection
TPOS01_P1EC_OK_CS
(5130018004011E81)
[TPOS01-PLSM]*
Fix
Var
Operate Failed
[TPOS01-RST]
ASEQ function§ is in progress
ASEQ_MULTI_SEL
TPOS01_P1EC_OK_CSF
(513001 8004011E7E)
TPOS01_EX_FFL
(513001 8604011E91) ‡‡
To Wait for a command
&
Detection of state-change in a device
&
PLC#2
TPOS01IN_TMP_38
513001 820401EE5E
User configurable condition
(PLC#2 connection point)
1
&
TPOS01_EX_CMP
(5130018004011E93)
Operate Completed
1.0s- 100.0s
0
t
ILK condition (“P1”) passed
TPOS1-P1
1
ILK bypassing
ICB_STATE
Figure 4.9-33 Operate ‘P1-control’ on the front panel TPOS01
††
Note: The ILK function can provide the operation criteria for P1” control.
Note: An operate condition signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #3 “User configurable condition” That is, set the scheme switch
[TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_28”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
††
Note: To identify the input and output signal-points of the P1-control in the other TPOS
logics, see Table 4.9-15 for PLC#1, Table 4.9-16 for PLC#2 and Table 4.9-20 for the
outputs.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST].

Table of Contents

Related product manuals