EasyManua.ls Logo

Toshiba GR200 Series - Page 976

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 953 -
Operate condition
TPOS01 function (Function ID: 513001)
User configurable condition (PLC connection point#2)
Fixedlogic
[TPOS01-LGSLFFCT]
To selection logic
Control hierarchy (e.g. 43RL) (PLC connection point#3) *10
IED serious error detected
[TPOS01-CTREN]
On
Users must setup this condition correctly
Function Automatic sequence control is in progress
Additional condition (PLC connection point #1)
CBK_STATE
Command blocking*1
Double Command Blocking detected*2
Other devices traveling detected*3
Tripping *4 (“General trip”)
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
GEN. TRIP
TPOS01IN_TMP_33
513001 800401EE65
TPOS01IN_TMP_34
513001 810401EE66
TPOS01IN_TMP_21
TPOS01IN_TMP_41
513001 820401ED50
SERI_ERR
&
&
&
&
1
1
Unmatched condition detected *5
Event suppression detected *6
= TPOS01_QLT_SPP
BI board connection error detected*7
= TPOS01_QLT_BI_ERR
(513001 8204011F59)
(513001 8604011F5A)
OFF
[SCDEN]*8
Same Directional
Controlling Event
&
P1-control command received
TPOS01_ST_P1
&
TPOS01_ST_P2
P2-control command received
&
TPOS01_ST_P3
P3-control command received
&
&
[TPOS01-DEVTYPE]*9
EDS
(513001 8304011D02)
(513001 8104011D03)
(513001 8504011D04)
“EDS” never permit to control
from “P1 to P3” and “P3 to P1”.
Figure 4.9-44 Operate condition logic for P1–3 control in TPOS01*
11
*1
Note: “Command Blocking” disables any operation except for itself; “Command
blocking” is implemented as CBKin a software switch controller (SOFTSW);.
The IEC 61850 defines “Command Blocking” as “CmdBlk”. For more information
of CBK, see Chapter
Control and monitoring application: Software switch
control function
. See the signal “CBK_STATE” in Table 4.9-6.
*2
Note: “Double Command Blocking (DCB)” is an operation philosophy. It can be used
to protect the substation. The user can program it using GR-TIEMS.
*3
Note: Detection of event “device-travelling signifies that other operators are
changing the status of one or more devices. Thus, device operation by the IED
should be inhibited whilst ever the event is detected. The detection signal is
denoted as “Traveling OR” in Table 4.9-6.
*4
Note: If an IED is in the process of issuing a trip command, all control operation is
blocked until the trip operation has been completed. If the IED has a relay
application, the trip command is issued at the output-point “GEN.TRIP” in Table

Table of Contents