(vii) Select condition
Figure 4.8-13 shows the select condition logic in the DPOS01 function. The DPOS01 function
checks the condition for the Select command using the signal DPOS1_3PH_STATE (see Table
4.8-32). If the original logic does not meet with the requirements of the user, the following
alternatives are available:
1. The user can replace the original logic with alternative logic,
2. The user can add additional logic to the original logic.
How to replace the original logic
If the user wishes to replace the select condition logic, the user can replace it using the PLC
connection point “User configurable condition”:
1. Connect the user-customized logic using DPOS01IN_TMP_31”, which is listed as
PLC#2 in Table 4.8-7.
2. Set the scheme switch [DPOS01-LGSLFFCT] to PLC.
How to add another select condition signal
If adding another condition is required, the user can add a signal using the PLC connection
point Additional condition.
1. Add a user-preferred signal using DPOS01IN_TMP_32”, which is listed as PLC#1 in
Table 4.8-7.
2. Set the scheme switch [DPOS01-LGSLFFCT] to Fixedlogic.