Group setting for protection functions
As shown in Figure 5.8-1, protection settings (i.e., OC settings, EF settings, etc.) are segmented
into eight groups, and different setting values of the relays can be set as per circumstances
such as operation conditions and others. Note that changing the group cannot be not carried
out instantly.
Settings
DOUT_BOOL
FID
DTYPE
DID
ST
DI
Protection (Relay)
Group1 setting
OC
EF
OV
UV
THM
TRC
Group2 setting
OC
EF
OV
UV
THM
TRC
Group8 setting
OC
EF
OV
UV
THM
TRC
Figure 5.8-1 Eight groups for protection settings
(i) Changing group number by menu operation
The user can change the group number using the menu on the IED screen. See the Chapter
User interface: Setting sub-menu.
(ii) Changing group number by user-programming
Another changing method is provided by programing PLC logics (For more information about
PLC programing, see the Chapter
PLC function.
) Figure 5.8-2 exemplifies a PLC logic:
changing group2 from group1 is performed while BI1 circuit is energized. The group setting
function Setting (Function ID 201400) has a signal reception point PLC_Group_ENUM in
UNIT type; thus changing the group is performed when either numbers (1 to 8) enters at the
signal reception point. The example logic, designed for changing to group2 from group1,