6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 457 -
(xii) Issuing close command – setting (TCCW1)
The logic for issuing close command for ARC1 and ARC2 is illustrated in Figure 2.34-22.
8000011B6C
ARC1 CLOSE COMMAND
0.01-10.00s
TCCW1
1
Shot1Shot5 for CB#1
ARC1 SHOT1
ARC1 SHOT2
ARC1 SHOT3
ARC1 SHOT4
ARC1 SHOT5
CB1_MANUAL_CLOSE
800001EBCD
ARC1 SHOT
Success check for CB#1
To BO
8100021B68
ARC2 CLOSE COMMAND
0.01-10.00s
TCCW2
1
Shot for CB#2
ARC2 SHOT
CB2_MANUAL_CLOSE
810002EBCA
ARC2 SHOT
Success check for CB#2
To BO
Figure 2.34-22 Issuing for CB#1 and CB#2