6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 637 -
(iii) Cancel condition logic
Figure 4.1-18 shows the cancel condition logic. As the criteria, “unmatched condition detected”
is connected normally for the cancel logic, set Fixlogic for the scheme switch
[SPOS01_LGCNFFC].
SPOS01 function (Function ID: 510001)
User configurable condition (PLC connection point)
Fixedlogic
[SPOS01-LGSLFFCT]
To cancel logic in
SPOS01
Unmatched condition detected *1
SPOS01IN_TMP_46
510001 800101EE69
&
&
1
Figure 4.1-18 Logic “Cancel condition” in SPOS01
1
Note: The Criteria “unmatched conditions” are determined when the “Test-bit status” in
the cancel command is not identical to the “IED test status”, like in Figure 4.1-13.
2
Note: With the exception of the above cancel condition logic, there is an operate-
condition logic within the SPOS01 function; the operate-condition logic will always
checks conditions. That is, the user is required to set either the “operate-
condition” or the “cancel-condition” logic.
If the original logic does not meet with the requirements of the user, it can be replaced
with another logic using the connection point “User Configurable condition”:
1. Connect the user-customized logic with the “SPOS01IN_TMP_46”.
2. Set scheme switch [SPOS01-LGCNFFCT] to PLC.
(iv) Signal name and number
Note: The user should note the following descriptions shown in the column M/O in
each table:
“O” indicates that the signal is provided for optional use.
M indicates that the user should map/set/configure using the signal;
otherwise, the user may experience an operational failure for the default
settings.
N/A indicates that the user cannot change the state of the signal.
Table 4.1-11 PLC connection points (Input signal forcancel condition)
Signal Number
Signal Name
Description
M/O
510001 800101EE69
SPOS01IN_TMP_46
SPOS01 user configurable cancel condition
O
510001 800102EE69
SPOS02IN_TMP_46
SPOS02 user configurable cancel condition
O
510001 800103EE69
SPOS03IN_TMP_46
SPOS03 user configurable cancel condition
O
510001 800114EE69
SPOS20IN_TMP_46
SPOS20 user configurable cancel condition
O
Table 4.1-12 PLC monitoring points (Output signal for cancel condition)
Signal Number
Signal Name
Description
510001 8601011E95
SPOS01_CC_SS
Cancel succeed in SPOS01