- 637 - 
 
(iii)  Cancel condition logic 
Figure 4.1-18 shows the cancel condition logic. As the criteria, “unmatched condition detected” 
is  connected  normally  for  the  cancel  logic,  set  Fixlogic  for  the  scheme  switch 
[SPOS01_LGCNFFC]. 
SPOS01  function  (Function  ID:  510001) 
User configurable condition (PLC connection point) 
To cancel logic in 
SPOS01 
Unmatched condition detected *1 
 
Figure 4.1-18 Logic “Cancel condition” in SPOS01 
1
Note: The Criteria “unmatched conditions” are determined when the “Test-bit status” in 
the cancel command is not identical to the “IED test status”, like in Figure 4.1-13. 
2
Note: With the exception of the above ‘cancel’ condition logic, there is an operate-
condition logic within the SPOS01 function; the operate-condition logic will always 
checks conditions. That is, the user is required to set either the “operate-
condition” or the “cancel-condition” logic. 
 
If the original logic does not meet with the requirements of the user, it can be replaced 
with another logic using the connection point “User Configurable condition”:   
1.  Connect the user-customized logic with the “SPOS01IN_TMP_46”. 
2.  Set scheme switch [SPOS01-LGCNFFCT] to PLC. 
 
(iv)  Signal name and number 
Note:  The user should note the following descriptions shown in the column “M/O” in 
each table: 
“O” indicates that the signal is provided for optional use. 
“M” indicates that the user should map/set/configure using the signal; 
otherwise, the user may experience an operational failure for the default 
settings. 
“N/A” indicates that the user cannot change the state of the signal. 
Table 4.1-11 PLC connection points (Input signal for ‘cancel’ condition) 
SPOS01 user configurable cancel condition 
SPOS02 user configurable cancel condition 
SPOS03 user configurable cancel condition 
SPOS20 user configurable cancel condition 
 
Table 4.1-12 PLC monitoring points (Output signal for ‘cancel’ condition)