EasyManua.ls Logo

Toshiba GR200 Series - 4.6.5 Relay selection for checking synchronization

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 814 -
4.6.5 Relay selection for checking synchronization
Figure 4.6-16 exemplifies a bus-bar arrangement used as an example for check synchronization.
In this example, the SYNCHK_Ry1 relays require the voltage signals V3, V4, and V1. This is
because DS1 and DS3 are closed, but DS2 is open; the selection of SYNCHK_Ry1 is initiated
by the reception of the SYNCHK_Ry1_selection signal. The SYNCHK_Ry1_selection and
SYNCHK_Ry2_selection signals are generated by logic programmed by the user; hence, here
the signal SYNCHK_Ry1_selection is connected with the PLC connection point
SYNC01_RY1_USE_STS”‡.
V3
V4
DS1
DS2
CB1
DS3
V1
DS3 closed
Selection of SYNCHK_Ry1
SYNCHK_Ry1_selection
Busbar#1
Line
Busbar#2
Running
line
SYNC01_RY1_USE_STS
&
DS3 closed
Selection of SYNCHK_Ry2
Ry1
Ry2
Incoming
line
SYNCHK01 function
DS1 open
DS2 closed
DS1 closed
&
&
Relay selection logic programmed by the user
using the PLC function
SYNCHK_Ry2_selection
SYNC01_RY2_USE_STS
Figure 4.6-16 Relay-selection-signal provided by DPSY function (an example)
Note: The relationship between the injected voltage-signals and the SYNCHK_Ry
function is discussed in section 4.6.6.
Note:The user should also connect the SYNCHK_Ry2_selection signal with the PLC
connection point SYNC01_RY2_USE_STS. Users should note that Figure 4.6-16
is provided for explanation/information; the user is required to program relay-
selection logic using the PLC function that responds dynamically to configuration
changes that occur as a consequence of CB and DS operations.
In Figure 4.6-16 , two signals are used for relay selection, but the user should note that
the selection-signals are provided in accordance with the actual line and bus-bar arrangement.
Figure 4.6-17 shows the overall logic used for the selection. The user can program the selection-
signals using the PLC function.

Table of Contents

Related product manuals