EasyManua.ls Logo

Toshiba GR200 Series - (ii) BO connection for “select command Open;Closing”; (iii) BO connection for “operate command Open;Closing”

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 715 -
operation of the detection function from Time A (e.g., Time A to Time C).
The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [DPSY-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time D to E).
To initiate event suppression the user should set On for scheme switch [DPSY01-SPPEN].
(ii) BO connection for select command Open/Closing”
Figure 4.2-43 exemplifies the connection for the select command Open/Closing. Suppose that
connection with the BOs is achieved by the PLC function using connection points
DPSY01_OSL_BO_FLG” and DPSY01_FSL_BO_FLG”†; as a result, the Select command
Closing” and the Select command Open” signals are issued at BO1 and BO2 respectively.
BO1_SOURCE
200B01 310200E11D
Select logic in DPSY01
PLC connection point on BO1
Select logic for Select Command
Closing in DPSY01
Select logic for Select Command
Open in DPSY01
≥1
&
[BO1_CPL]
Off
On
&
DRIVER
BO1
Signal captured by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
Select
Command
Closing
≥1
BO1
(200B01_8002001112)
BO1-RB
(200B01_8002001113)
BO1 circuit at IO#1(Function ID: 200B01)
Terminal and
wire
To contact health
check
Connected by
Programming
To contact health
check
BO2_SOURCE
200B01 310201E11D
PLC connection point on BO2
≥1
&
[BO2_CPL]
Off
On
&
DRIVER
BO2
Signal captured by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
≥1
BO2
(200B01_8102011112)
BO2-RB
(200B01_8102011113)
BO2 circuit at IO#1 (Function ID: 200B01)
Terminal and
wire
To contact health
check
Connected by
Programming
To contact health
check
DPSY01_OSL_BO_FLG
(5110018602011DC6)
DPSY01_FSL_BO_FLG
(511001 8A02011DC4)
Select
Command
Open
Figure 4.2-43 Example for select commands connection with BO1 & BO2 at IO#1
Note: Table 4.2-10 shows the remaining signals with the excepting
DPSY01_OSL_BO_FLG” and DPSY01_FSL_BO_FLG.
(iii) BO connection for operate command Open/Closing”
Figure 4.2-44 exemplifies the connection for “Operate command Closing” or “Operate command
Open”. Suppose that connection with the BOs is achieved by the PLC function using connection

Table of Contents

Related product manuals