6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 684 -
Table 4.2-5 PLC connection points (Interlock for Command ‘Closing/Open’)
Signal Number
Signal Name
Description
M/O
570001 3102011DA2
DPSY01-Open
DPSY01 interlock condition for Open control.
N/A
570001 3102021DA2
DPSY02-Open
DPSY02 interlock condition for Open control.
N/A
570001 3102011DA0
DPSY01-Close
DPSY01 interlock condition for Close control.
N/A
570001 3102021DA0
DPSY02-Close
DPSY02 interlock condition for Close control.
N/A
Table 4.2-6 Mapping points for the reception of control commands
Signal Number
Signal Name
Description
M/O
511001 7002016D08
DEV01_CONTROL_REQ
DPSY01 control command received.(Mapping Data)
M
511001 7002026D08
DEV02_CONTROL_REQ
DPSY02 control command received. (Mapping Data)
M
Table 4.2-7 Input signals to condition logic
Signal Number
Signal Name
Description
M/O
570001 3103011DA2
ASEQ_MULTI_SEL
Automatic sequence control is in progress.
N/A
522001 000A011001
CBK_STATE
Command Blocking status ( Open / Blocked)
N/A
522001 000A021001
ICB_STATE
Interlock-Bypassing Switch
N/A
522001 000A031001
SCB_STATE
Synch-Bypassing Switch
N/A
5A0001 0008001F41
DCB RCV OR
Double Command Blocking(DCB) is in progress.
N/A
5A0001 0008001F40
Traveling OR
Travelling events are detected.
N/A
4A0001 8300001B6F
GEN. TRIP
General trip
N/A
5A0001 3108003F40
SDCEN
(This is setting of CMNCTRL)
N/A
5A0101 3100001F43
SERI_ERR
Serious Error detected
N/A
Table 4.2-8 PLC connection points (Input signals for select condition logic)
Signal Number
Signal Name
Description
M/O
511001 800531EF40
DPSY01IN_TMP_31
DPSY01 additional failure condition(PLC#1)
O
511001 800554EF40
DPSY02IN_TMP_31
DPSY02 additional failure condition(PLC#1)
O
511001 800532EF40
DPSY01IN_TMP_32
DPSY01 user configurable select condition(PLC#2)
O
511001 800555EF40
DPSY02IN_TMP_32
DPSY02 user configurable select condition(PLC#2)
O
511001 800516EF40
DPSY01IN_TMP_28
DPSY01 control hierarchy condition(PLC#3)
M
511001 800519EF40
DPSY02IN_TMP_28
DPSY02 control hierarchy condition(PLC#3)
M
Table 4.2-9 PLC monitoring points (Output signal for select condition logic)
Signal Number
Signal Name
Description
511001 8002011F5A
DPSY01_SC_ST_ERR
DPSY01 Unmatched condition.
511001 8002021F5A
DPSY02_SC_ST_ERR
DPSY02 Unmatched condition.
511001 8102011F5F
DPSY01_F_QLT_SPP
Event suppression detected (DPSY01)
511001 8102021F5F
DPSY02_F_QLT_SPP
Event suppression detected (DPSY02)
511001 8202011F60
DPSY01_F_BI_ERR
BI connection error detected(DPSY01)
511001 8202021F60
DPSY02_F_BI_ERR
BI connection error detected(DPSY02)
Table 4.2-10 PLC monitoring points (Closing/Open output signals for BIO)
Signal Number
Signal Name
Description
511001 8602011DC6
DPSY01_OSL_BO_FLG
DPSY01 select (Closing) command for Binary Output.
511001 8602021DC6
DPSY02_OSL_BO_FLG
DPSY02 select (Closing) command for Binary Output.
511001 8A02011DC4
DPSY01_FSL_BO_FLG
DPSY01 select (Open) command for Binary Output.
511001 8A02021DC4
DPSY02_FSL_BO_FLG
DPSY02 select (Open) command for Binary Output.