Toshiba GR200 Series - (i)-2 Output signal to BO

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 641 -
§§Note: The “SPOS01_OEX-BO” signal is issued when Fixlogic is set for scheme switch
[SPOS01-LGCFEXOT]. The “Operate completed “signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.1-20. The
user-programmed logic is connected internally to the signal “Operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point # 2 “user-configurable condition”. That is, set the scheme switch [SPOS01-
LGCFEXOT] to PLC and use “SPOS01IN_TMP_42”.
Output signal to BO
The SPOS01 function, in Figure 4.1-20, can issue an Operate” signal at the output point
“SPOS01_OEX_BO”, when the SPOS01 function determines that the received signal “Remote-
On-Control is true.