6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 259 -
2.16.8 Data ID
Signal monitoring point
EF(Function ID: 441001)
Element ID
Name
Description
8500001B62
EF-ARC-BLOCK
Block for issuing autoreclose signal in the EF function
8400001B61
EF-OPT-ALARM
Alarm signal issued in EF function
8300001B23
EF-OPT-TRIP
Trip signal issued in EF function
8000011C23
EF1
EF1 relay element operated
8200011B62
EF1-ARC-BLOCK
Block for issuing autoreclose signal in the EF1 element
8000011B60
EF1-OPT
EF1 protection operated
8100011B61
EF1-OPT-ALARM
Alarm signal in EF1 element
8000011B23
EF1-OPT-TRIP
Trip signal issued in EF1 element
8000011C27
EF1PU
Pick up signal in IDMT in EF1 element
8000011B63
EF1_BLOCK
Command to block the EF1 element
8000011B64
EF1_INST_OP
Command to operate the EF1 element instantly
8100021C23
EF2
EF2 relay element operated
8200021B62
EF2-ARC-BLOCK
Block for issuing autoreclose signal in the EF2 element
8100021B60
EF2-OPT
EF2 protection operated
8100021B61
EF2-OPT-ALARM
Alarm signal in EF2 element
8000021B23
EF2-OPT-TRIP
Trip signal issued in EF2 element
8100021C27
EF2PU
Pick up signal in IDMT in EF2 element
8100021B63
EF2_BLOCK
Command to block the EF2 element
8100021B64
EF2_INST_OP
Command to operate the EF2 element instantly
8200031C23
EF3
EF3 relay element operated
8200031B62
EF3-ARC-BLOCK
Block for issuing autoreclose signal in the EF3 element
8200031B60
EF3-OPT
EF3 protection operated
8100031B61
EF3-OPT-ALARM
Alarm signal in EF3 element
8000031B23
EF3-OPT-TRIP
Trip signal issued in EF3 element
8200031C27
EF3PU
Pick up signal in IDMT in EF3 element
8200031B63
EF3_BLOCK
Command to block the EF3 element
8200031B64
EF3_INST_OP
Command to operate the EF3 element instantly
8300041C23
EF4
EF4 relay element operated
8200041B62
EF4-ARC-BLOCK
Block for issuing autoreclose signal in the EF4 element
8300041B60
EF4-OPT
EF4 protection operated
8100041B61
EF4-OPT-ALARM
Alarm signal in EF4 element
8000041B23
EF4-OPT-TRIP
Trip signal issued in EF4 element
8300041C27
EF4PU
Pick up signal in IDMT in EF4 element
8300041B63
EF4_BLOCK
Command to block the EF4 element
8300041B64
EF4_INST_OP
Command to operate the EF4 element instantly
Connection point on PLC logic
EF(Function ID: 441001)
Element ID
Name
Description
800001EBB0
EF1_BLOCK
EF1 protection block command
800001EBB1
EF1_INST_OP
EF1 protection instant operation command
810002EBB0
EF2_BLOCK
EF2 protection block command
810002EBB1
EF2_INST_OP
EF2 protection instant operation command

Table of Contents