EasyManua.ls Logo

Toshiba GR200 Series - Page 281

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 258 -
EF(Function ID:441001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
EF4-Rtimer
DEF / DEP
-
EF4 reset delay type of US
DEF
TEF4R
0.00 - 300.00
s
EF4 definite time reset delay
0.00
EF4-RTMS-US
0.010 - 50.000
-
EF4 dependent reset time multiplier of US
inverse curve
1.000
ORG
EF4
0.02 -
5.00
0.10 -
25.00
A
EF4 threshold (in IDMT mode)
0.30
1.50
EF4-DPR
10 - 100
%
EF4 drop-out/pick-up ratio
100
EF4-TMS-ORG
0.010 - 50.000
-
EF4 time multiplier of Original inverse curve
1.000
EF4-Rtimer
DEF / DEP
-
EF4 reset delay type of ORG
DEF
TEF4R
0.00 - 300.00
s
EF4 definite time reset delay
0.00
EF4-RTMS-
ORG
0.010 - 50.000
-
EF4 dependent reset time multiplier of
Original inverse curve
1.000
EF4-k
0.00000 - 500.00000
-
EF4 user original curve coefficient
0.00000
EF4-a
0.00000 - 10.00000
-
EF4 user original curve coefficient
0.00000
EF4-c
0.00000 - 10.00000
-
EF4 user original curve coefficient
0.00000
EF4-kr
0.00000 - 500.00000
-
EF4 user original curve coefficient
0.00000
EF4-b
0.00000 - 10.00000
-
EF4 user original curve coefficient
0.00000
Output
EF4-VTFBlk
Non / Block
-
EF4 operation block by VTF
Non
EF4-CTFBlk
Non / Block
-
EF4 operation block by CTF
Non
EF4-UseFor
Trip / Alarm
-
EF4 used for trip or alarm
Trip
EF4-ARCBlk
Non / Block
-
Autoreclose block by EF4
Block