6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 257 -
EF(Function ID:441001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
ORG
EF3
0.02 -
5.00
0.10 -
25.00
A
EF3 threshold (in IDMT mode)
0.30
1.50
EF3-DPR
10 - 100
%
EF3 drop-out/pick-up ratio
100
EF3-TMS-ORG
0.010 - 50.000
-
EF3 time multiplier of Original inverse curve
1.000
EF3-Rtimer
DEF / DEP
-
EF3 reset delay type of ORG
DEF
TEF3R
0.00 - 300.00
s
EF3 definite time reset delay
0.00
EF3-RTMS-
ORG
0.010 - 50.000
-
EF3 dependent reset time multiplier of
Original inverse curve
1.000
EF3-k
0.00000 - 500.00000
-
EF3 user original curve coefficient
0.00000
EF3-a
0.00000 - 10.00000
-
EF3 user original curve coefficient
0.00000
EF3-c
0.00000 - 10.00000
-
EF3 user original curve coefficient
0.00000
EF3-kr
0.00000 - 500.00000
-
EF3 user original curve coefficient
0.00000
EF3-b
0.00000 - 10.00000
-
EF3 user original curve coefficient
0.00000
Output
EF3-VTFBlk
Non / Block
-
EF3 operation block by VTF
Non
EF3-CTFBlk
Non / Block
-
EF3 operation block by CTF
Non
EF3-UseFor
Trip / Alarm
-
EF3 used for trip or alarm
Trip
EF3-ARCBlk
Non / Block
-
Autoreclose block by EF3
Block
EF4
EF4-Dir
NonDir / Forward /
Reverse
-
EF4 directional characteristic
NonDir
Fwd/
EF4-Angle
0 - 180
deg
EF4 directional characteristic angle
45
Rev
EF4-Vpol
0.5 - 100.0
V
EF4 polarizing voltage level
3.0
EF4-Timer
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
IEEE-EI / US-CO2 /
US-CO8 / Original
-
EF4 delay type
DT
DT
EF4
0.02 -
50.00
0.10 -
250.00
A
EF4 threshold (in DT mode)
0.30
1.50
EF4-DPR
10 - 100
%
EF4 drop-out/pick-up ratio
100
TEF4
0.00 - 300.00
s
EF4 operating delay time (in DT mode)
1.00
IEC
EF4
0.02 -
5.00
0.10 -
25.00
A
EF4 threshold (in IDMT mode)
0.30
1.50
EF4-DPR
10 - 100
%
EF4 drop-out/pick-up ratio
100
EF4-TMS-IEC
0.010 - 50.000
-
EF4 time multiplier of IEC inverse curve
1.000
TEF4R
0.00 - 300.00
s
EF4 definite time reset delay
0.00
UK
EF4
0.02 -
5.00
0.10 -
25.00
A
EF4 threshold (in IDMT mode)
0.30
1.50
EF4-DPR
10 - 100
%
EF4 drop-out/pick-up ratio
100
EF4-TMS-UK
0.010 - 50.000
-
EF4 time multiplier of UK inverse curve
1.000
TEF4R
0.00 - 300.00
s
EF4 definite time reset delay
0.00
IEEE
EF4
0.02 -
5.00
0.10 -
25.00
A
EF4 threshold (in IDMT mode)
0.30
1.50
EF4-DPR
10 - 100
%
EF4 drop-out/pick-up ratio
100
EF4-TMS-
IEEE
0.010 - 50.000
-
EF4 time multiplier of IEEE inverse curve
1.000
EF4-Rtimer
DEF / DEP
-
EF4 reset delay type of IEEE
DEF
TEF4R
0.00 - 300.00
s
EF4 definite time reset delay
0.00
EF4-RTMS-
IEEE
0.010 - 50.000
-
EF4 dependent reset time multiplier of IEEE
inverse curve
1.000
US
EF4
0.02 -
5.00
0.10 -
25.00
A
EF4 threshold (in IDMT mode)
0.30
1.50
EF4-DPR
10 - 100
%
EF4 drop-out/pick-up ratio
100
EF4-TMS-US
0.010 - 50.000
-
EF4 time multiplier of US inverse curve
1.000