Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 256 -
EF(Function ID:441001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
EF2-Rtimer
DEF / DEP
-
EF2 reset delay type ORG
DEF
TEF2R
0.00 - 300.00
s
EF2 definite time reset delay
0.00
EF2-RTMS-
ORG
0.010 - 50.000
-
EF2 dependent reset time multiplier of
Original inverse curve
1.000
EF2-k
0.00000 - 500.00000
-
EF2 user original curve coefficient
0.00000
EF2-a
0.00000 - 10.00000
-
EF2 user original curve coefficient
0.00000
EF2-c
0.00000 - 10.00000
-
EF2 user original curve coefficient
0.00000
EF2-kr
0.00000 - 500.00000
-
EF2 user original curve coefficient
0.00000
EF2-b
0.00000 - 10.00000
-
EF2 user original curve coefficient
0.00000
Output
EF2-VTFBlk
Non / Block
-
EF2 operation block by VTF
Non
EF2-CTFBlk
Non / Block
-
EF2 operation block by CTF
Non
EF2-UseFor
Trip / Alarm
-
EF2 used for trip or alarm
Trip
EF2-ARCBlk
Non / Block
-
Autoreclose block by EF2
Block
EF3
EF3-Dir
NonDir / Forward /
Reverse
-
EF3 directional characteristic
NonDir
Fwd/
EF3-Angle
0 - 180
deg
EF3 directional characteristic angle
45
Rev
EF3-Vpol
0.5 - 100.0
V
EF3 polarizing voltage level
3.0
EF3-Timer
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
IEEE-EI / US-CO2 /
US-CO8 / Original
-
EF3 delay type
DT
DT
EF3
0.02 -
50.00
0.10 -
250.00
A
EF3 threshold (in DT mode)
0.30
1.50
EF3-DPR
10 - 100
%
EF3 drop-out/pick-up ratio
100
TEF3
0.00 - 300.00
s
EF3 operating delay time (in DT mode)
1.00
IEC
EF3
0.02 -
5.00
0.10 -
25.00
A
EF3 threshold (in IDMT mode)
0.30
1.50
EF3-DPR
10 - 100
%
EF3 drop-out/pick-up ratio
100
EF3-TMS-IEC
0.010 - 50.000
-
EF3 time multiplier of IEC inverse curve
1.000
TEF3R
0.00 - 300.00
s
EF3 definite time reset delay
0.00
UK
EF3
0.02 -
5.00
0.10 -
25.00
A
EF3 threshold (in IDMT mode)
0.30
1.50
EF3-DPR
10 - 100
%
EF3 drop-out/pick-up ratio
100
EF3-TMS-UK
0.010 - 50.000
-
EF3 time multiplier of UK inverse curve
1.000
TEF3R
0.00 - 300.00
s
EF3 definite time reset delay
0.00
IEEE
EF3
0.02 -
5.00
0.10 -
25.00
A
EF3 threshold (in IDMT mode)
0.30
1.50
EF3-DPR
10 - 100
%
EF3 drop-out/pick-up ratio
100
EF3-TMS-
IEEE
0.010 - 50.000
-
EF3 time multiplier of IEEE inverse curve
1.000
EF3-Rtimer
DEF / DEP
-
EF3 reset delay type of IEEE
DEF
TEF3R
0.00 - 300.00
s
EF3 definite time reset delay
0.00
EF3-RTMS-
IEEE
0.010 - 50.000
-
EF3 dependent reset time multiplier of IEEE
inverse curve
1.000
US
EF3
0.02 -
5.00
0.10 -
25.00
A
EF3 threshold (in IDMT mode)
0.30
1.50
EF3-DPR
10 - 100
%
EF3 drop-out/pick-up ratio
100
EF3-TMS-US
0.010 - 50.000
-
EF3 time multiplier of US inverse curve
1.000
EF4-Rtimer
DEF / DEP
-
EF3 reset delay type of US
DEF
TEF3R
0.00 - 300.00
s
EF3 definite time reset delay
0.00
EF3-RTMS-US
0.010 - 50.000
-
EF3 dependent reset time multiplier of US
inverse curve
1.000

Table of Contents