6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 63 -
Header
Ia3
Ib3
Ic3
COM5
CRC
a. Receiving frames from Remote-1 IED in IEEE C37.94
N=3
8310061C85
8410061C86
8510061C87
COMM_ APPL function (Function ID: 4A9001)
RDIF function
R1.DIFL-A_OP
800000EBB8
R1.DIFL-B_OP
810000EBB9
R1.DIFL-C_OP
820000EBBA
R2.DIFL-A_OP
800000EBBB
R2.DIFL-B_OP
810000EBBC
R2.DIFL-C_OP
820000EBBD
8000001BB6
8100001BB7
8200001BB8
8000001BB9
8100001BBA
8200001BBB
To DIFL
Header
Ia3
Ib3
Ic3
COM5
CRC
b. Receiving frames from Remote-2 IED in IEEE C37.94
N=3
COM5-5-R1
COM5-4-R1
COM5-6-R1
To DIFL
CRC (8bits)
COM5 (6bits)
1
2
3
4
5
6
CRC (8bits)
CRC
CRC (8bits)
COM5 (6bits)
1
2
3
4
5
6
CRC (8bits)
CRC
8310071CAD
8410071CAE
8510071CAF
COM5-5-R2
COM5-4-R2
COM5-6-R2
Figure 2.6-5 Mapping for reception signals using COM5 bits
Note: For more information, see
Chapter Relay application: Communication application
.
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH].
(ii) Operation of TFC countermeasure in DIFLG
The user should set On for scheme switch [DIFGL-TFC-EN] when the TFC countermeasure is
required in the DIFGL function. Note that Off is set in the scheme switch, as default.
Sending DIFGL operation signal for the opposite
The signals of the DIFGL elements should be exchanged mutually for the both terminals.
Figure 2.6-6 shows the DIFGL elements; the operated signal DIFGL is set for the opposite
by the communication.
DIFGL#1
1
8000001C23
DIFGL#2
DIFGL
Figure 2.6-6 Sending DIFGL operation signal for remote terminals