- 62 -
2.6-4 exemplifies the points: “R1.DIFL-A_OP, R1.DIFL-B_OP, R1.DIFL-C_OP” for the Remote-
1_IED, “R2.DIFL-A, R2.DIFL-B, R2.DIFL-C_OP” for the Remote-2_IED. The received signals
are sent to the DIFL main-logic in Figure 2.2-3.
Figure 2.6-4 Reception logic for TFC operation
Figure 2.6-5 (a) exemplifies the receiving signals from the Remote-1_IED using the
COM3-4, COM3-5, COM3-6 bits; as for the example, we can map the PLC connection points
“COM3-4_R1, COM3-5_R1, COM3-6_R1” with PLC connection points “R1.DIFL-A, R1.DIFL-
B, R1.DIFL-C_OP”. Similarly, Figure 2.6-5 (b) exemplifies that we can map the signals from
the Remote-2_IED with other PLC connection points.