- 475 -
Voltage check for autoreclose (VCHK)
The voltage-check-for-autoreclose (VCHK) function is used along with the function of
autoreclose (ARC), as Bus-bar between Lines requires the restoration of service after the
clearance of fault.
The ARC covers two breaker systems: single breaker system (1CB) and single-and-a-half
breaker system (1.5CB), and the ARC has two scheme logics: one scheme logic (ARC1) is for
1CB and for Bus-bar CB of 1.5CB, and another scheme logic (ARC2) is for Center CB of 1.5CB.
Thus, the VCHK consist of two scheme logics (VCHK1 and VCHK2), and VCHK1 is applied to
ARC1; on the other hand, VCHK2 is used for ARC2.
b. One-and-a-half breaker on system (1.5CB)
a. Single breaker on system (1CB)
Figure 2.35-1 Single breaker and double breakers on the system
─────────────────────────────────────────────────────────────────
Note: To determine whether the features are implemented in the IED or not, locate the IED
ordering number; and check the order number at “G&T position” referring to the comparison
table below. For more information, see
Appendix: Ordering
.
Table 2.35-1 Comparative table in respective ordering numbers
Voltage check for Auto-reclosing
✓: Applicable NA: Not applicable