- 717 -
Setting for “Select command Closing”
For example, the point DPSY01_OSL_BO_FLG is connected to the BO1 circuit for the issuing
of the command; the user can connect point BO1-RB with the contact health check function
using the setting [DPSY01-OSLBORD]. Do not key the point “DPSY01_OSL_BO_FLG”.
DPSY01_OSL_BO_FLG
(511001 8602011DC6)
Selection logic in
DPSY01
&
Signal connected by
setting [DPSY01-OSLBORD]
BO1-RB
(200B01_8002001113)
BO1 circuit at
IO#1
Contact health check
logic in DPSY01
Result of contact
health check
Connection made by the user
Figure 4.2-45 Example connection of “Select command Closing” for the health check feature
Setting the “Select command Open”
Similar to select command Closing”, the point DPSY01_FSL_BO_FLG is connected with the
BO2 circuit; the user is required to key point BO2-RB for the setting [DPSY01-FSLBORD].
Do not key the point DPSY01_FSL_BO_FLG.
DPSY01_FSL_BO_FLG
(511001 8A02011DC4)
Selection logic in
DPSY01
&
Signal connected by
setting [DPSY01-FSLBORD]
BO2-RB
(200B01_8102001113)
BO1 circuit at
IO#1
Contact health check
logic in DPSY01
Result of contact
health check
Connection made by the user
Figure 4.2-46 Example connection of “Select command Open” for the health check feature
Setting for “Operate command Closing”
Similarly, the point BO3-RB must be applied for the setting [DPSY01-OEXBORD].