5.3.3 Communication modules
The tables below show piggyback-circuit-modules provided for the communication. They are
mounted on CPU module directly. The actual mountings depend on the user ordering; thus,
the user should locate the actual implementations by the ordering using
Appendixes
:
Ordering
and
Typical external connection
.
Table 5.3-1 Communication modules for Protection
Module
Protection signaling
Protection signaling
Connector
ST type
LC type (Duplex)
Medium
Fiber optic(GI)
Fiber optic(SM/DSF)
Usage
Tele-protection (2km class)
Tele-Protection (30km / 80 km class)
Symbol
RX
TX
Protection
Protection
RX
TX
Table 5.3-2 Communication modules for Network
Module
100Base-TX/1000Base-T
100Base-FX
1000Base-LX
Connector
RJ45 type
SC type (Duplex)
LC type (Duplex)
Medium
Shielded twist pair
Fiber optic
Fiber optic
Usage
Substation automation
system and others
Substation automation
system and others
Substation automation
system and others
Symbol
100/1000
BASE-T
RX
TX
100BASE-X
1000
BASE-LX
Table 5.3-3 Communication modules for Miscellaneous
Module
RS485
Fiber optic interface
IRIG-B
Connector
PCB connector
ST type
PCB connector
Medium
Shielded twist pair
Fiber optic(GI)
Shielded twist pair
Usage
Data transfer in
IEC103
Data transfer in
IEC103 (2km class)
Time
synchronization
Symbol
RS485
A1
B1
COM-A
A2
B2
COM-B
A3
B3
COMM
RX
TX
Remote
Comm.
IRIG-B000
A1
B1
SIG
A2(Disuse)
B2(Disuse)
A3
B3
GND