EasyManua.ls Logo

Toshiba GR200 Series - 2.9 Stub protection with overcurrent relay (STUB-OC)

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 86 -
Stub protection with overcurrent relay (STUB-OC)
Figure 2.9-1 depicts that a one-and-a-half breaker (1.5CBs) arrangement with a transmission
line including a disconnector (DS). An area stub zone’ is defined within two CBs and the DS,
which is expressed by hatching in the figure.
For the 1.5CB arrangement, a voltage transformer (VT) is generally installed along the
line GH. Figure 2.9-1 shows that the line GH is taken out of service because of the DS being
open; hence, a distance relay in the IED_G cannot detect a fault when a fault occurs in the
stub zone. This is because a faulted voltage cannot be measured correctly using the VT
G
.
Thereby, an overcurrent relay (OC) is provided to protect the stub zone and the OC relay
operates speedy upon occurrence of the fault.
CT2
G
CT1
G
Terminal-G
Fault
IED_G
IED_H
CT2
H
CT1
H
Terminal-H
Line GH
Line
DS
CB
CB
CB
Line
VT
G
CB
VT
H
CB
CB
Figure 2.9-1 Fault occurred in stub zone
(2.44.1)
─────────────────────────────────────────────────────────────────
Note: The implementation of such features is dependent upon the selection of hardware and
the configuration of functions. Several IED models do not support certain features. To
determine whether a particular feature has been implemented within an IED, identify the IED
ordering number; and check the order number at the G&T position referring to the
comparison table below. For more information, see
Appendix: Ordering
.
Table 2.9-1 Comparative table in respective ordering numbers
Section
feature
Relay function/ features
Ordering No. at G&T
33
37
STUB-OC
OC relay for stub protection
: Applicable NA: Not applicable

Table of Contents

Related product manuals