- 911 -
(ii) Receiving “select command P2-control” from the remote-end
Figure 4.9-4 outlines the reception of the select command ‘P2-control’ from the remote-end.
Signal reception
IEC61850
P2 control from the remote-end
P3 control from the remote-end
P1 control from the local-end
P2 control from the local-end
P3 control from the local-end
P1 control by the PLC function
P2 control by the PLC function
P3 control by the PLC function
P1 control from the remote-end
Figure 4.9-4 Outline of select command ‘P2-control’
Input point mapped from the communication
Figure 4.9-5 shows the select logic when a “Select command P2 (Remote-P2-Control)” signal is
received at the input-point “DEV01_CONTROL_REQ”.
TPOS01 function (Function ID: 513001)
“TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
Command “P2-Control” from the remote
ILK† condition (“P2”) passed
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*)
Selection logic in TPOS01
“Automatic sequence control function (AQEQ)§” in progress
Select command
with ILK† condition
Operate command
with ILK† condition
Select command
without ILK† condition
Operate command
without ILK† condition
Figure 4.9-5 Select P2-control from the remote-end in TPOS01
††
†Note: The ILK function provides the operation criteria for “P2-control”.
††
Note: To identify the input and output points of the other TPOS logics, see Table