- 320 -
†Note: For more information of the trip circuit, see Chapter
Relay application: Trip
circuit
.
(iii) Execution of OVG function
Set On for scheme switch [OVG1-EN]. Otherwise, set Off for the scheme switch [OVG1-EN] if
the OVG1 element is not required to operate.
2.23.5 Scheme logic
Figure 2.23-4 shows the OVG function logic. Signal connection points “OVG*_BLOCK” are
provided for the block of the operation of the OV elements. For testing, the OVG1-PU element
is provided; it generates a pick-up signal when the entering voltage is excesses of the threshold
anytime. Thereby, in the IDMT characteristic, using both monitoring points “8000011C23” and
“8000011C27” can facilitate to measure the pickup time after the excess.
Figure 2.23-4 OVG function logics