6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1485 -
Figure 12.8-10 Binary output menu
Figure 12.8-11 shows selection of IO#2 (Slot #2).
Figure 12.8-11 Setting menu for Slot #2 module
Figure 12.8-12 shows the Output Circuit configuration of BO01 at IO#2 (Slot#2).
The procedure for operation is similar to the operation of the binary input circuit.
(Refer to Figure 12.8-7 to Figure 12.8-9)
Figure 12.8-12 Setting menu after selecting “SLOT2-BO01-SET
The user can configure the required settings for the simulation test of the binary
output circuit.
ON: Output signal for simulation test is ON
OFF: Output signal for simulation test is OFF
Normal: Actual inputs are applied.
(iii) TestFlag-EN screen
This function can set all communication protocol Test flags to Test mode. The user should select
TestFlag-EN in Figure 12.8-1 and select On or Off.
Binary Output
10:48 1/2
Slot#2 >
Slot#3 >
Slot#2
10:48 1/19
BO2F OP +
SLOT2-BO01-SET +
Normal
SLOT2-BO02-SET +
Normal
SLOT2-BO02-SET +
SLOT2-BO01-SET
10:48 1/3
Normal
Off
On