6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1716 -
DPOS01 setting (exercise)
We need to set [DPOS01-EN]=On for DPOS01 in order that we can control the CB by MIMIC
at local-end. Table 4 and Figure 6 show the setting items in the DPOS01 controlling.
DPOS inputs
When [DPOS01-CTRN]=On is set for general CB controls (#1), we can make settings NOPSG
(N/O) and NCLSG (N/C) to get CB aux. contact signals in DPOS01.
[DPOS01A-NOPSG]=BI1 and [DPOS01A-NCLSG]=BI2 (#2, #3)
[DPOS01B-NOPSG]=BI1 and [DPOS01B-NCLSG]=BI2 (#4, #5)
[DPOS01C-NOPSG]=BI1 and [DPOS01C-NCLSG]=BI2 (#6, #7)
DPOS outputs
When [DPOS01-PLSM]= Var is set, OPEN or CLOSE command will be issued if Closing or
Opening keys are pushed (#8).
We need have setting [DPOS01-FEXBORD]=BO3 RE (#9) in order that the command has been
issued without discrepancy (see Figure 5). Similarly, we have the setting [DPOS01-
OEXBORD]=BO4 RE (#10).
Table 4 Exercise in DPOS01 (Function ID: 512001)
Step
Signals/ [Settings]
Signal/[Setting] contents
0
[DPOS01-EN]
DPOS01 ready switch
1
[DPOS01-CTRN]
DPOS01 switch
2
[DPOS01A-NOPSG]
N/O setting at phase-A
BI1
BI1 circuit output
3
[DPOS01A-NCLSG]
N/C setting at phase-A
BI2
BI2 circuit output
4
[DPOS01B-NOPSG]
N/O setting at phase-B
BI1
BI1 circuit output
5
[DPOS01B-NCLSG]
N/C signal at phase-B
BI2
BI2 circuit output
6
[DPOS01C-NOPSG]
N/O setting at phase-C
BI1
BI1 circuit output
7
[DPOS01C-NCLSG]
N/C setting at phase-C
BI2
BI2 circuit output
8
[DPOS01-PLSM]
OPEN/CLOSE pulse adjustment
9
[DPOS01-FEXBORD]
OPEN validity setting
BO4 RE
Read-back signal on BO4 circuit
10
[DPOS01-OEXBORD]
CLOSE validity setting
BO3 RE
Read-back signal on BO3 circuit