- 1716 -
DPOS01 setting (exercise)
We need to set [DPOS01-EN]=On for DPOS01 in order that we can control the CB by MIMIC
at local-end. Table 4 and Figure 6 show the setting items in the DPOS01 controlling.
DPOS inputs
When [DPOS01-CTRN]=On is set for general CB controls (#1), we can make settings NOPSG
(N/O) and NCLSG (N/C) to get CB aux. contact signals in DPOS01.
[DPOS01A-NOPSG]=BI1 and [DPOS01A-NCLSG]=BI2 (#2, #3)
[DPOS01B-NOPSG]=BI1 and [DPOS01B-NCLSG]=BI2 (#4, #5)
[DPOS01C-NOPSG]=BI1 and [DPOS01C-NCLSG]=BI2 (#6, #7)
DPOS outputs
When [DPOS01-PLSM]= Var is set, OPEN or CLOSE command will be issued if Closing or
Opening keys are pushed (#8).
We need have setting [DPOS01-FEXBORD]=BO3 RE (#9) in order that the command has been
issued without discrepancy (see Figure 5). Similarly, we have the setting [DPOS01-
OEXBORD]=BO4 RE (#10).
Table 4 Exercise in DPOS01 (Function ID: 512001)
Signal/[Setting] contents
OPEN/CLOSE pulse adjustment
Read-back signal on BO4 circuit
Read-back signal on BO3 circuit