Toshiba GR200 Series - (i)-2 Defining DIR setting mode; (ii) Mapping output data

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 663 -
SBOw
Oper
Cancel
Origin
stSeld
sboClass (choice operate-once)
ctlmodel (choice SBOes or SBOns )
sboClass can be found by scrolling down.
Figure 4.1-41 LN editing screen for SBO (for example)
Defining DIR setting mode
Figure 4.1-42 exemplifies the SPOS01 logic node saved as GGIO1501. In the DIR mode, the
following three items should be selected using GR-TIEMS:
Oper
origin
ctlmodel (choice DOes or DOns )
Figure 4.1-42 LN editing screen for DIR mode (for example)
(ii) Mapping output data
The user should group the SPOS01 signals with regard to GOOSE and Report; the user should
map them for IEC 61850 communication using GR-TIEMS. Figure 4.1-43 illustrates how to
map a signal; it indicates that the signals for the SPOS01 function are required to be mapped
for IEC 61850 communication.