6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 974 -
example can issue a select command; which is called operated by internal select function.
The user does not need to consider the use of a BO circuit for a select command, when there
are no BO circuits available.
Table 4.9-33 Extra setting example for contact health check
Example #3
Setting for example #3
TPOS01_P1SL_BO_FLG is not connected to any BO
TPOS01_P1SL_BO_FLG set for [TPOS01-P1SLBORD]
OK
TPOS01_P2SL_BO_FLG is not connected to any BO
TPOS01_P2SL_BO_FLG set for [TPOS01-P2SLBORD]
OK
TPOS01_P3SL_BO_FLG is not connected to any BO
TPOS01_P3SL_BO_FLG set for [TPOS01-P3SLBORD]
OK
TPOS01_P1EX_BO” is connected to BO4 on SLOT1
200B01 8302031113(BO4-RB) set for [TPOS01-P1EXBORD]
OK
TPOS01_P2EX_BO” is connected to BO5 on SLOT1
200B01 8402041113(BO5-RB) set for [TPOS01-P2EXBORD]
OK
TPOS01_P3EX_BO” is connected to BO6 on SLOT1
200B01 8502051113(BO6-RB) set for [TPOS01-P3EXBORD]
OK
Plus (+)
TPOS01_P1SL_BO_FLG
(513001 8A04011DC4)
BO1
Drivers
P1-select
command
BO4
P1-operate
command
TPOS01_P1EX_BO
(513001 8104011DD0)
BO4-RB
(200B01 8302031113)
Remote/Local end
P1-Operate
BOs are not connected but virtualized.
BIO module
P2-Operate
P2-Selection
P3-Operate
P3-Selection
Minus ()
TPOS01_P2SL_BO_FLG
(513001 8A04011DC6)
BO2
P2-select
command
BO2-RB
(200B01 8102011113)
BO5
P2-operate
command
TPOS01_P2EX_BO
(513001 8204011DD3)
BO5-RB
(200B01 8402041113)
TPOS01_P3SL_BO_FLG
(513001 8A04011DC8)
P3-select
command
BO6
P3-operate
command
TPOS01_P3EX_BO
(513001 8204031DD3
BO6-RB
(200B01 8502051113)
EDS
BO1 (not BO1-RB)
mistakenly chosen with
200B01 8002001112
SAS/Local IED
Figure 4.9-63 Contact health check setting and EDS diagram for example #3
(v) Signal name and number
Table 4.9-34 PLC monitoring points (Output signal for event suppression function in TPOSxx)
Signal Number
Signal Name
Description
513001 8204011F59
TPOS01_QLT_SPP
Event suppression detected (TPOS01)