- 974 -
example can issue a select command; which is called “operated by internal select function”.
The user does not need to consider the use of a BO circuit for a select command, when there
are no BO circuits available.
Table 4.9-33 Extra setting example for contact health check
“TPOS01_P1SL_BO_FLG” is not connected to any BO
“TPOS01_P1SL_BO_FLG” set for [TPOS01-P1SLBORD]
“TPOS01_P2SL_BO_FLG” is not connected to any BO
“TPOS01_P2SL_BO_FLG” set for [TPOS01-P2SLBORD]
“TPOS01_P3SL_BO_FLG” is not connected to any BO
“TPOS01_P3SL_BO_FLG” set for [TPOS01-P3SLBORD]
“TPOS01_P1EX_BO” is connected to “BO4” on SLOT1
200B01 8302031113(BO4-RB) set for [TPOS01-P1EXBORD]
“TPOS01_P2EX_BO” is connected to “BO5” on SLOT1
200B01 8402041113(BO5-RB) set for [TPOS01-P2EXBORD]
“TPOS01_P3EX_BO” is connected to “BO6” on SLOT1
200B01 8502051113(BO6-RB) set for [TPOS01-P3EXBORD]
“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
“TPOS01_P1EX_BO”
(513001 8104011DD0)
“BO4-RB”
(200B01 8302031113)
BOs are not connected but virtualized.
“TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
“BO2-RB”
(200B01 8102011113)
“TPOS01_P2EX_BO”
(513001 8204011DD3)
“BO5-RB”
(200B01 8402041113)
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
“TPOS01_P3EX_BO”
(513001 8204031DD3
“BO6-RB”
(200B01 8502051113)
“BO1” (not BO1-RB)
mistakenly chosen with
200B01 8002001112
Figure 4.9-63 Contact health check setting and EDS diagram for example #3
(v) Signal name and number
Table 4.9-34 PLC monitoring points (Output signal for event suppression function in TPOSxx)
Event suppression detected (TPOS01)