EasyManua.ls Logo

Toshiba GR200 Series - 4.9.8 Setting

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 980 -
4.9.8 Setting
TPOS01(FunctionID:513001)
Setting items
Range
Unit
Contents
Default
Note
Commo
n
TPOS-NELD
0 - 99
-
Number of Event lock detect time
10
TPOS-TELD
1 - 99
s
Timer of detect event lock
10
TPOS-TELR
1 - 99
s
Timer of recovery from event lock
10
TPOS01-EN
Off / On
-
TPOS01 switch for Device01
Off
Dev01
TPOS01-DEVNAME
[Preferred text]
-
item name of TPOS_Dev1
TPOS_Dev1
!
TPOS01-000NAME
[Preferred text]
-
state name of (0,0,0)state
Travelling0
!
TPOS01-001NAME
[Preferred text]
-
state name of (0,0,1)state
P1
!
TPOS01-010NAME
[Preferred text]
-
state name of (0,1,0)state
P2
!
TPOS01-011NAME
[Preferred text]
-
state name of (0,1,1)state
Travelling1
!
TPOS01-100NAME
[Preferred text]
-
state name of (1,0,0)state
P3
!
TPOS01-101NAME
[Preferred text]
-
state name of (1,0,1)state
Travelling2
!
TPOS01-110NAME
[Preferred text]
-
state name of (1,1,0)state
Travelling3
!
TPOS01-111NAME
[Preferred text]
-
state name of (1,1,1)state
Travelling4
!
TPOS01-UDFNAME
[Preferred text]
-
state name of undefined
Undefine
!
TPOS01-FLTNAME
[Preferred text]
-
state name of faulty
Faulty
!
TPOS01-DEVTYPE
switch / EDS
-
Device Type
switch
TPOS01-P1NOPSG
[Preferred signal]
-
P1 Normally Open Signal of Dev1
Not assigned
TPOS01-P1NOPSGI
Off / On
-
Signal inverse or not
Off
TPOS01-P2NOPSG
[Preferred signal]
-
P2 Normally Open Signal of Dev1
Not assigned
TPOS01-P2NOPSGI
Off / On
-
Signal inverse or not
Off
TPOS01-P3NOPSG
[Preferred signal]
-
P3 Normally Open Signal of Dev1
Not assigned
TPOS01-P3NOPSGI
Off / On
-
Signal inverse or not
Off
TPOS01-SPPEN
Off / On
-
Automatic event suppression function
Off
TPOS01-UDFEN
Off / On /
CHKONLY
-
undefined pallet check function
Off
TPOS01-UDFTIM
0.1 - 100.0
s
palette undefined check timer
30.0
TPOS01-FLTEN
Off / On /
CHKONLY
-
faulty pallet check function
Off
TPOS01-FLTTIM
0.1 - 100.0
s
palette faulty check timer
30.0
TPOS01-CTREN
Off / On
-
control mode (control enable)
Off
TPOS01-CTRMENU
Off / On
-
control by MENU enable
Off
TPOS01-CTRAHMI
DIR / SBO
-
control action(Direct or SBO)by HMI
SBO
TPOS01-NSLBORD1
[Preferred signal]
-
select binary output read data(DataID)1 for no
direction command
5130018904011DC0
TPOS01-NSLBORD2
[Preferred signal]
-
select binary output read data(DataID)2 for no
direction command
5130018904011DC0
TPOS01-NSLBORD3
[Preferred signal]
-
select binary output read data(DataID)3 for no
direction command
5130018904011DC0
TPOS01-P1SLBORD
[Preferred signal]
-
select binary output read data(DataID) for P1
direction command
5130018A04011DC4
TPOS01-P2SLBORD
[Preferred signal]
-
select binary output read data(DataID) for P2
direction command
5130018A04011DC6
TPOS01-P3SLBORD
[Preferred signal]
-
select binary output read data(DataID) for P3
direction command
5130018A04011DC8
TPOS01-P1EXBORD
[Preferred signal]
-
execute binary output read data(DataID) for
P1 direction command
Not assigned
TPOS01-P2EXBORD
[Preferred signal]
-
execute binary output read data(DataID) for
P2 direction command
Not assigned
TPOS01-P3EXBORD
[Preferred signal]
-
execute binary output read data(DataID) for
P3 direction command
Not assigned
TPOS01-LGCTRCON
FixedLogic /
PLC
-
Change logic about control condition
FixedLogic