6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 981 -
TPOS01(FunctionID:513001)
Setting items
Range
Unit
Contents
Default
Note
TPOS01-LGSLFFCT
FixedLogic /
PLC
-
Change logic about select fail factor
FixedLogic
TPOS01-LGEXFFCT
FixedLogic /
PLC
-
Change logic about execute command fail
factor
FixedLogic
TPOS01-LGP1EXOT
FixedLogic /
PLC
-
Change logic about P1 direction execute
output
FixedLogic
TPOS01-LGP2EXOT
FixedLogic /
PLC
-
Change logic about P2 direction execute
output
FixedLogic
TPOS01-LGP3EXOT
FixedLogic /
PLC
-
Change logic about P3 direction execute
output
FixedLogic
TPOS01-LGCNFFCT
FixedLogic /
PLC
-
Change logic about cancel command fail factor
FixedLogic
TPOS01-PLSM
Fix / Var
-
pulse mode
Fix
TPOS01-CPW
0.1 - 50.0
s
control pulse width
1.0
TPOS01-RST
1.0 - 100.0
s
response check timer
30.0
TPOS01-CTRDIR
P1 / P2 / P3
-
Capable control direction
P2
TPOS01-P1CNTS
Off / On
-
P1 count status
Off
TPOS01-P2CNTS
Off / On
-
P2 count status
Off
TPOS01-P3CNTS
Off / On
-
P3 count status
Off
TPOS01-OPETMEN
Off / On
-
Operation Time Measurement enable
Off
TPOS01-APBD
Process / Bay
-
status change origin
Process
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The TPOS function is available for a 2
nd
Device and other devices. We have
omitted the others because this will be the same as the 1
st
device with the
exception of the device number.