EasyManua.ls Logo

Toshiba GR200 Series - 11.4.6 Protocol selection

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1424 -
11.4.6 Protocol selection
As shown in the setting menu for the Communication (Figure 11.4-11), the user should set
IEC103 for the [Slave Protocol] so that the communication in the IEC60870-5-103 standard is
carried out in the IED. Note that the restarting the IED (i.e., resetting the IED power) is
required after the user turns to the IEC60870-5-103 protocol.
Communication
10:48 1/3
LAN >
USBCOM >
SLAVE PROTOCOL >
SLAVE PROTOCOL
10:48 1/1
Slave Protocol +
IEC103
SLAVE PROTOCOL
10:48 1/4
IEC61850
IEC103
DNP3.0
Modbus
Figure 11.4-11 Slave protection for the IEC103 protocol (on IED setting menu)
Note: This sample menu illustrates how to select the IEC103, so that we do not discuss
the inclusion of IEC61850, DNP3.0, and Modbus and the selection of those
protocols here. See Figure 11.1-1 to check the inclusion of the protocols in the IED.