EasyManua.ls Logo

Toshiba GR200 Series - 2.20.6 Setting

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 298 -
2.20.6 Setting
CBF(Function ID: 453001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
CBF-EN
Off / On
-
CBF protection scheme switch
Off
OC
OCCBF-EN
Off / On
-
Current flow is judged by OC relay operation
On
OCCBF1
0.10 -
5.00
0.50 -
25.00
A
OCCBF1 relay operating level (Current flow
judgment)
1.00
5.00
OCCBF2
0.10 -
5.00
0.50 -
25.00
A
OCCBF2 relay operating level (Current flow
judgment)
1.00
5.00
EF
EFCBF-EN
Off / On
-
Current flow is judged by EF relay operation
Off
EFCBF1
0.10 -
5.00
0.50 -
25.00
A
EFCBF1 relay operating level (Current flow
judgment)
1.00
5.00
EFCBF2
0.10 -
5.00
0.50 -
25.00
A
EFCBF2 relay operating level (Current flow
judgment)
1.00
5.00
Timer
TCBF1-RE
0.000 - 300.000
s
CBF1 retrip timer
0.150
TCBF1-TP
0.000 - 300.000
s
CBF1 trip timer
0.200
TCBF2-RE
0.000 - 300.000
s
CBF2 retrip timer
0.150
TCBF2-TP
0.000 - 300.000
s
CBF2 trip timer
0.200
Output
CBF1-Retrip
Off / On / On-T
-
CBF1 retrip operation mode
On
CBF1-Trip
Off / On / On-AftRe
-
CBF1 trip operation mode
On
CBF2-Retrip
Off / On / On-T
-
CBF2 retrip operation mode
On
CBF2-Trip
Off / On / On-AftRe
-
CBF2 trip operation mode
On

Table of Contents

Related product manuals