4.8.3 Operate logic for SBO/DIR modes
Once the operation of the select logic is complete, the operate logic start to control the device.
(i) Receiving “Operate command On” from the remote-end
Figure 4.8-19 depicts the reception of the operate command On from the remote-end.
Signal reception in
IEC61850
Operate command On from the remote-end
Do nothing
Operation
decision
Success
Failed
Operate logic
Wait for a command
Signal output
Operate command On from the local-end
Operate command Off from the local-end
Operate command Off from the remote-end
Operate command On by the PLC function
Operate command Off by the PLC function
Wait for a next command
Select stage
Select command Off from the remote-end
Select command On from the remote-end
Select command Off from the local-end
Select command On from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Figure 4.8-19 Outline of Operate command ‘On
Mapping required for Input point
Figure 4.8-20 illustrates the operate logic when an Operate command On (Remote-ON-
Control)” signal is applied to the DPOS01 function. The input-point “DEV01_CONTROL_REQ”
is used for the reception of the Operate command On (Remote-On-Control)”.
Output signal to BO
The DPOS01 function, in Figure 4.8-20, can issue an Operate” signal at the output point
DPOS01_OEX_BO”, when the DPOS01 function determines that the received signal Remote-
On-Control is true.