EasyManua.ls Logo

Toshiba GR200 Series - (i)-2 Decision by input signals

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 966 -
TPOS01_QLT_SPP. The former one is used in the select condition logic and the
operate condition (see Figure 4.9-20 and Figure 4.9-44). The latter is used for an
event suppression detector.
Decision by input signals
The logic in Figure 4.9-55 can give a decision in response to the reception of the signals; the
decision is of either P1, P2, P3, Faulty, and “Intermediate”. Table 4.9-30 exemplifies the
decisions in response to the BI1 - BI3 input signals; the decision can be acquired at the
monitoring point TPOS01_STATE.
Suppose, the BI1BI3 circuits receive OnOffOff signals when an earth-switch is
located at P1(see Figure 4.9-1); the value 1 is given, because the decision can be made with
the “OnOffOff signals.
If OnOnOff signals are applied to the BI1BI3 circuits, the decision cannot be made
because the earth switch is still kinetic and is not standstill; thus, the decision is given as
“Intermediate”, the value 3 is given at the connection point ”TPOS01_STATE”.
If OnOnOn signals are applied to the BI1BI3 circuits, the decision cannot be made
because the earth-switch may be broken; hence, the value 7 is given.
Table 4.9-30 Decision made by the TPOS01 function
Input signals at IO#1 (200B01)
Decision by
TPOS01
Generated value
“TPOS01_STATE”
(513001 3104011001)
BI1
(8001001110)
BI2
(8101011110)
BI3
(8201021110)
Off (0)
Off (0)
Off (0)
Intermediate
0
On (1)
Off (0)
Off (0)
P1
1
Off (0)
On (1)
Off (0)
P2
2
On (1)
On (1)
Off (0)
Intermediate
3
Off (0)
Off (0)
On (1)
P3
4
On (1)
Off (0)
On (1)
Intermediate
5
Off (0)
On (1)
On (1)
Intermediate
6
On (1)
On (1)
On (1)
Faulty
7
Note: When handling the raw information other than the decision, the user can take
respective states of binary input circuits using other monitoring points. That is,
the user can take either state On (1) or state Off (0) corresponding to the BI1
circuit using the monitoring point TOPS01_PT_P1. Likewise, the BI2 and BI3
states can be taken using the monitoring points TOPS01_PT_P2 and
TOPS01_PT_P3. (See Table 4.9-35)

Table of Contents

Related product manuals