Toshiba GR200 Series - (iv)-2 Output signal to BO; (v) Receiving “operate command P2-control” from the local-end; (v)-1 Input signal generated at the local-end.

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 942 -
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for the scheme
switch [TPOS01-LGP1EXOT]. The “Operate completed” signal can also be issued
from the logic programmed by the user in place of the logic shown in Figure
4.9-26. The user-programmed logic is connected internally to the “operate
completed”, hence this signal is now generated by the user-programmed logic at
connection point#2 “User configurable condition”. That is, set the scheme switch
[TPOS01-LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.9-33, can issue an Operate” signal at the output point
“TPOS01_P1EX_BO”, when the TPOS01 function determines that the Local-P1-Control
signal is true.
(v) Receiving “operate command P2-control” from the local-end
Figure 4.9-34 depicts the reception of the operate command P2-control from the local-end.
Signal reception from
the front panel
P2 control from the local-end
Do nothing
Operation
decision
Success
Failed
Operate logic
P1 control from the remote-end
P2 control from the remote-end
P3 control from the remote end
P1 control from the local-end
P1 control by the PLC function
P3 control from the local-end
P2 control by the PLC function
Wait for a command
P2 control from the local-end
P3 control by the PLC function
Select logics
Signal output
P3 control from the remote end
P1 control from the local-end
P1 control from the remote-end
P2 control from the remote-end
P3 control from the local-end
P1 control by the PLC function
P2 control by the PLC function
P3 control by the PLC function
Wait for a next command
Figure 4.9-34 Outline of Operate command ‘P2-control’
Input signal generated at the local-end.
Figure 4.9-35 illustrates the operate logic when an Operation command P2 (Local-P2-Control)
signal is applied to the TPOS01 function. The input signal is provided when P2-control is
keyed on the IED front panel.