- 943 -
TPOS01 function (Function ID: 513001)
Operate Cmd.
with ILK† condition
Operate Cmd.
without ILK† condition
Command Local-P2-Control”
User configurable condition (PLC#3 connection point)
“TPOS01_P2EC_OK_CSF”
(513001 8004011E7F)
“TPOS01_P2EX_BO”
(513001 8204011DD3) §§
“TPOS01_P2EC_OK_CS”
(513001 8304011E82)
ASEQ function§” is in progress
“TPOS01_P2EC_OK_CSF”
(513001 8004011E7F)
“TPOS01_EX_FFL”
(513001 8604011E91) ‡‡
Detection of state-change in a device
User configurable condition
(PLC#2 connection point)
“TPOS01_EX_CMP”
(513001 8004011E93)
ILK† condition (“P2”) passed
Figure 4.9-35 Operate ‘P2-control’ on the front panel in TPOS01
††
†Note: The ILK function can provide the operation criteria for “P2” control.
‡Note: An “operate condition” signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative “operate-condition” can be connected to the to the above logic using
connection point #3 “User configurable condition” That is, set the [TPOS01-
LGCTRCON] to PLC and using “ TPOS01IN_TMP_28”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [TPOS01-RST].
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for the [TPOS01-
LGP1EXOT]. The “Operate completed” signal can also be issued from the logic
programmed by the user in place of the logic shown in Figure 4.9-26 . The user-
programmed logic is connected internally to the signal “operate completed”, hence