TPOS01 function (Function ID: 513001)
Assign to BOs
Operate Cmd.
with ILK condition
S
R
0.1 50.0 s
[TPOS01-CPW]
Operate Cmd.
without ILK condition
Operate condition
[TPOS01-LGCTRCON]
Fixedlogic
Fixedlogic
[TPOS01-LGP2EXOT]
DEV01_CONTROL_REQ
Command Local-P2-Control
513001_7004016D08
TPOS01IN_TMP_28
513001 810401EE57
User configurable condition (PLC#3 connection point)
TPOS01_P2EC_OK_CSF
(513001 8004011E7F)
&
&
1
&
1
1
&
&
&
TPOS01_P2EX_BO
(513001 8204011DD3) §§
Input
Output
Operate logic in TPOS01
To BO connection
TPOS01_P2EC_OK_CS
(513001 8304011E82)
[TPOS01-PLSM]*
Fix
Var
Operate Failed
[TPOS01-RST]
ASEQ function§ is in progress
ASEQ_MULTI_SEL
TPOS01_P2EC_OK_CSF
(513001 8004011E7F)
TPOS01_EX_FFL
(513001 8604011E91) ‡‡
To Wait for a command
&
Detection of state-change in a device
&
TPOS01IN_TMP_38
513001 820401EE5E
User configurable condition
(PLC#2 connection point)
1
&
TPOS01_EX_CMP
(513001 8004011E93)
Operate Completed
1.0s- 100.0s
0
t
ILK condition (“P2”) passed
TPOS1-P2
1
ILK bypassing
ICB_STATE
Figure 4.9-35 Operate ‘P2-control’ on the front panel in TPOS01
††
Note: The ILK function can provide the operation criteria for P2” control.
Note: An operate condition signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition is required it can be programmed by the user and
used to replace the signal generated by the original operate-condition logic. The
alternative “operate-condition” can be connected to the to the above logic using
connection point #3 “User configurable condition” That is, set the [TPOS01-
LGCTRCON] to PLC and using “ TPOS01IN_TMP_28”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the [TPOS01-RST].
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for the [TPOS01-
LGP1EXOT]. The “Operate completed” signal can also be issued from the logic
programmed by the user in place of the logic shown in Figure 4.9-26 . The user-
programmed logic is connected internally to the signal “operate completed”, hence