-  281  - 
 
2.18.2  Thermal characteristic 
THM characteristics are determined with two equations. Equation (2.18-3) is used to define 
the cold state. Equation (2.18-4) is used to define the hot state: 
  
 
 
 
where t is time to trip for a constant overload current of I (minutes), I is the overload current 
(largest phase current in amperes), I
AOL
 is the permitted overload current (amperes), Ip is the 
pre-load current (amperes), τ is the thermal time constant (minutes), and Ln is the natural 
logarithm. 
 
In Equation (2.18-3), cold curves are special versions of the hot curves where Ip is zero, 
catering for the situation where a cold system is switched onto an immediate overload. 
 
Figure  2.18-1.a  shows  the  cold  state  where  an  overload  has  been  switched  onto  a 
previously un-loaded system. Figure 2.18-1.b shows the hot state where an overload is switched 
onto  a  system  that  has  previously  been  loaded  to  90%  of  its  capacity.  The  figures  are  in 
conformity with the IEC 60255-149 curves, and these curves are drawn in a range of settings 
of the time constant ().   
a.Thermal Curves (Cold Curve - no prior load) 
b. Thermal Curves (Hot Curve - 90%  prior load)) 
 
Figure 2.18-1 Thermal curves