EasyManua.ls Logo

Toshiba GR200 Series - 2.18.2 Thermal characteristic

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 281 -
2.18.2 Thermal characteristic
THM characteristics are determined with two equations. Equation (2.18-3) is used to define
the cold state. Equation (2.18-4) is used to define the hot state:
󰇩

󰇪
(2.18-3)
󰇩

󰇪
(2.18-4)
where t is time to trip for a constant overload current of I (minutes), I is the overload current
(largest phase current in amperes), I
AOL
is the permitted overload current (amperes), Ip is the
pre-load current (amperes), τ is the thermal time constant (minutes), and Ln is the natural
logarithm.
In Equation (2.18-3), cold curves are special versions of the hot curves where Ip is zero,
catering for the situation where a cold system is switched onto an immediate overload.
Figure 2.18-1.a shows the cold state where an overload has been switched onto a
previously un-loaded system. Figure 2.18-1.b shows the hot state where an overload is switched
onto a system that has previously been loaded to 90% of its capacity. The figures are in
conformity with the IEC 60255-149 curves, and these curves are drawn in a range of settings
of the time constant ().
a.Thermal Curves (Cold Curve - no prior load)
b. Thermal Curves (Hot Curve - 90% prior load))
100
50
20
10
5
1
Figure 2.18-1 Thermal curves

Table of Contents

Related product manuals