6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 939 -
TPOS01 function (Function ID: 513001)
Assign to BOs
Operate Cmd.
with ILK condition
S
R
0.1 50.0 s
[TPOS01-CPW]
Operation Cmd.
without ILK condition
Operate condition
[TPOS01-LGCTRCON]
Fixedlogic
Fixedlogic
[TPOS01-LGP3EXOT]
DEV01_CONTROL_REQ
Command Remote-P3-Control
513001_7004016D08
ILK condition (“P3”) passed
TPOS1-P3
TPOS01IN_TMP_29
513001 840401EE58
User configurable condition
(PLC#4 connection point)
TPOS01_P3EC_OK_CSF
(5513001 8004011E80)
&
&
1
&
1
1
&
&
&
TPOS01_P3EX_BO
(513001 8204011DD6) §§
Input
Output
Operate logic in TPOS01
To BO connection
TPOS01_P3EC_OK_CS
(513001 8404011E83)
[TPOS01-PLSM]*
Fix
Var
Operation Failed
[TPOS01-RST]
ASEQ function§ is in progress
ASEQ_MULTI_SEL
TPOS01_P3EC_OK_CSF
(513001 8004011E80)
TPOS01_EX_FFL
(513001 8604011E91) ‡‡
To Wait for a command
&
Detection of state-change in a device
&
TPOS01IN_TMP_38
513001 820401EE5E
User configurable condition
(PLC#2 connection point)
1
&
TPOS01_EX_CMP
(5130018004011E93)
Operation Completed
1.0s- 100.0s
0
t
Figure 4.9-31 Operate ‘P3-control’ from the remote-end in TPOS01
††
Note: The ILK function can provide the operation criteria for P3” control.
††
Note: To identify the input and output signals of the other TPOS logics, see Table
4.9-16 for PLC#2, Table 4.9-18 for PLC#4, and Table 4.9-20 for the outputs.
Note: An operate condition signal is generated inthe operate-condition logic (Figure
4.9-44) when Fix logic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” is required, it can be programmed by the user
and used to replace the signal generated by the original operate-condition logic.
The alternative “operate-condition” can be connected to the above logic using
connection point #4 “User configurable condition” That is, set the scheme switch
[TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_29”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set for the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST]
§§Note: The “TPOS01-PIEX-BO” signal is issued when Fixlogic is set for scheme switch
[TPOS01-LGP1EXOT]. The “Operate-completed” signal can also be issued from