6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 875 -
DPOS01 function (Function ID: 512001)
Assign to BOs
Operate Cmd.
with ILK condition
[DPOS01-PLSM]*
Fix
Var
S
R
Operate Failed
0
t
1.0s- 100.0s
0.1 50.0 s
[DPOS01-RST]
[DPOS01-CPW]
Operation Cmd.
without ILK condition
Operate condition
[DPOS01-LGCTRCON]
Fixedlogic
Fixedlogic
[DPOS01-LGCFEXOT]
ILK condition (“Open”) passed
DPOS01-Open
ASEQ function§ is in progress
ASEQ_MULTI_SEL
DPOS01IN_TMP_34
512001 800301EE56
User configurable condition
(PLC#1 connection point)
DPOS01_FEC_OK_CSF
(512001 8003011E7E)
DPOS01_FEC_OK_CSF
(512001 8003011E7E)
&
&
1
&
1
1
&
&
&
DPOS01_FEX_BO
(512001 8103011DD0)
DPOS01_EX_FFL
(512001 8603011E91)
Input
Output
Operate logic in DPOS01
PLC#1
To BO connection
To Wait for a command
DPOS01_FEC_OK_CS
(512001 8003011E81)
&
Detection of state-change in a device
&
PLC#2
DPOS01IN_TMP_42
512001 820301EE5E
User configurable condition
(PLC#2 connection point)
1
&
DPOS01_EX_CMP
(512001 8003011E93)
Operate Completed
Command PLC-On-Control with ILK
(PLC#3 connection point)
DEV01_OP_INTERLOCK
512001 800301EE31
Command PLC-On-Control without ILK
(PLC#4 connection point)
DEV01_OP_COMMAND
512001 800301EE30
Figure 4.8-30 Operate ‘Off by the PLC function in DPOS01
††
Note: The ILK function can provide the criteria for operation for control of the “Off
operation.
Note: An “operate condition signal is generated in the operate-condition logic (see
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative “operate-condition” programmed by the user is required in place of
the signal generated by the original operate-condition logic, connect the
alternative “operate-condition” to the logic shown in Figure 4.8-30 using
connection point #1 “User configurable condition. That is set the scheme switch
[DPOS01-LGCTRCON] to PLC and use “DPOS01IN_TMP_34.
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for the scheme
switch [DPOS01-LGCFEXOT]. If the signal is to be issued from the programmed
logic by the user in place of the logic in Figure 4.8-20, connect the signal “Operate
completed” generated in the programmed logic to the connection point #2 “User
configurable condition”. That is, set the scheme switch [DPOS01-LGCFEXOT] to
PLC and use “DPOS01IN_TMP_42”.
*Note: The user can select a type of the output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting applied
to [DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is