6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 728 -
DPSY01(FunctionID:511001)
Setting items
Range
Unit
Contents
Default
Note
DPSY01-LGCTRCON
FixedLogic /
PLC
-
Change logic about control condition
FixedLogic
DPSY01-LGSLFFCT
FixedLogic /
PLC
-
Change logic about select fail factor
FixedLogic
DPSY01-LGEXFFCT
FixedLogic /
PLC
-
Change logic about execute command fail
factor
FixedLogic
DPSY01-LGFEXOT
FixedLogic /
PLC
-
Change logic about off direction execute
output
FixedLogic
DPSY01-LGOEXOT
FixedLogic /
PLC
-
Change logic about on direction execute
output
FixedLogic
DPSY01-LGCNFFCT
FixedLogic /
PLC
-
Change logic about cancel command fail factor
FixedLogic
DPSY01-PLSM
Fix / Var
-
pulse mode
Fix
DPSY01-CPW
0.1 - 50.0
s
control pulse width
1.0
DPSY01-RST
1.0 - 100.0
s
response check timer
30.0
DPSY01-CNTS
NA / C-On / C-
Off / C-OnOff
-
count status
NA
DPSY01-OPETMEN
Off / On
-
Operation Time Measurement enable
Off
DPSY01-APBD
Process / Bay
-
status change origin
Process
DPSY01-CTRDIR
Off / On
-
Capable control direction
On
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The DPSY function is also available for the second device; hence, the table for 2
nd
device is available, but we have omitted the 2
nd
table because it is similar to the
table for the 1
st
device with the exception of the device number.