- 847 -
Selection logic in DPOS01
Command “Local-On-Control”
ILK† condition (“ON”) passed
DPOS01 function (Function ID: 512001)
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*)
“Automatic sequence control function (AQEQ)§” in progress
“DPOS01_OSL_BO_CSF”
(512001_8603011DC6)
Select command
with ILK† condition
Operate command
with ILK† condition
To “Wait for a next
command”
Figure 4.8-6 Select ‘On’ on the front panel in DPOS01
††
†Note: The ILK function provides the operation criterion for “On”. For testing, nullifying
the ILK function is possible using “Interlock bypassing”. “Interlock bypassing” is
indicated by the status “ICB” in a software switch controller (SOFTSW).
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
.
††
Note: To identify the output signals of the other DPOS logics, see Table 4.8-9.