6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 845 -
DPOS01_FSL_BO_FLG
(512001_8A01011DC4)
DPOS01 function (Function ID: 512001)
DEV01_CONTROL_REQ
Command Remote-Off-Control
ILK condition (“Off”) passed
Either SBO mode or DIR mode
(e.g., “ctlmodel” in IEC61850*)
In SBO operate
In DIR operate
Select Failed
512001_7001016D08
DPOS01-Open
To BO connection
Input
Output
Selection logic in DPOS01
0.1s
0
t
0.6s
0
t
&
&
&
&
&
Select success
Automatic sequence control function (AQEQ)§ in progress
ASEQ_MULTI_SEL
Select condition
1
Select command
with ILK condition
Operate command
with ILK condition
Select command
without ILK condition
Operate command
without ILK condition
For SBO operation
For DIR operation
To Wait for a command
For DIR operation
For SBO operation
Figure 4.8-4 Select ‘Off from the remote-end in DPOS01
††
Note: The ILK function provides the operation criteria for “Off”.
Note: Aselect condition signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information of the ASEQ function, see Chapter
Control
and monitoring application: Automatic sequence control function
.
††
Note: To know the input and output points of the other DPOS logics, see Table 4.8-5
and Table 4.8-9.