- 444 - 
 
Signal ‘1’ is generated when there is no contradiction between the 
various signals, that is only one signal is picking up. 
 
Figure 2.34-11 ARC1-MODE input logic 
When FT is selected, the ARC function send ‘CB1_BRIDGE’ signal for the TRC function 
to be the CB being tripped in three-phases, regardless of the condition of the tripped phase, 
the operation of respective protection elements, and the ARC settings; the ARC function does 
not operate (i.e., ARC1-FT). 
 
When TPAR is selected, the TRC and the ARC functions operate by the rule that the CB 
is tripped in three-phases and can be reclosed. That is, ‘CB1_BRIDGE’ signal is sent for the 
TRC function so that the CB will be tripped in three-phases forcibly even if a GEN.TRIP-A 
(TRIP COMMAND-A) signal is only generated in the TRC function (as well as GEN.TRIP-B 
and GEN.TRIP-C). Note the CB will be tripped in three-phases forcibly, even if a single-phase 
fault is detected and instructed a single-phase tripping by the relay applications.