6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 271 -
IEEE-MI
IEEE-VI
IEC-VI
IEC-EI
UK-LTI
ORIGINAL
IEEE-EI
US-C02
US-C08
IEC-NI
DT
OCN1_Timer
8000011C23
0.00-300.00s
BLOCK
BLOCK
OCN1-EN
ON
&
&
≥1
OCN1-VTFBLK
OCN1-CTFBLK
0
TOCN1
t
&
≥1
OCN1 PU
8000011C27
ICD-OR
&
≥1
&
&
&
8000011B60
OCN1
From ICD
From VTF
800001EBB0 OCN1_BLOCK
800001EBB1 OCN1_INST_OP
VTF_DETECT
CTF_DETECT
From CTF
TRIP
ALARM
OCN1-ARCBLK
OCN1-USEFOR
OCN1-OPT
&
&
&
OCN1-OPT-TRIP
OCN1-OPT-ALARM
OCN1-ARC-BLOCK
BLOCK
For DT characteristic
For IDMT characteristic
&
&
&
OCN1-2PBlk
Block
To Grouping logic
OCN1
OCN1PU
8000011BB0
8000011BB1
Figure 2.17-6 Scheme logic of OCN1
Note: The presence of OCN1 and OCN1PU signals depends on the operation
characteristic defined with setting [OCN1_Timer], as shown in Table 2.17-5.
Table 2.17-5 Signal behaviors of PLC monitoring points ‘OCN1’ and ‘OCN1PU’
PLC monitoring points
Setting [OCN1_Type]
DT
IEC-NT,VI,EI, UK-LTI, IEET-MI,VI,EI, US-CO2,CO8, ORIGINAL
OCN1
1
3
OCN1PU
2
4
1 : A pick-up signal is generated instantly when the element operates.
2 : No signal due that the PU element is killed. Use OCN1 in place of this.
3 : A pick-up signal is generated, but delayed with the IDMT characteristic.
4 : A pick-up signal is generated instantly.
To TRC
OCN1-OPT-TRIP
≥1
OCN2-OPT-TRIP
OCN3-OPT-TRIP
OCN4-OPT-TRIP
OCN-OPT-TRIP
OCN1-OPT-ALARM
≥1
OCN2-OPT- ALARM
OCN3-OPT- ALARM
OCN4-OPT- ALARM
OCN-OPT-ALARM
OCN1-ARC-BLOCK
≥1
OCN2- ARC-BLOCK
OCN3- ARC-BLOCK
OCN4- ARC-BLOCK
OCN-ARC-BLEFK
From OCN1 to OCN4 logics
OCN1-OPT
OCN2-OPT
OCN3-OPT
OCN4-OPT
OCN1-OPT
OCN2-OPT
OCN3-OPT
OCN4OPT
To Recording
Figure 2.17-7 Grouping logic for TRC/Recording