- 869 -
DPOS1 function (Function ID: 512001)
Operate Cmd.
with ILK† condition
Operate Cmd.
without ILK† condition
Command “Local-On-Control”
ILK† condition (“ON”) passed
User configurable condition (PLC#1 connection point)
“DPOS01_OEC_OK_CSF”
(512001 8003011E7F)
“DPOS01_OEC_OK_CS”
(512001 8103011E82)
ASEQ function§” is in progress
“DPOS01_EX_FFL”
††
(512001 8603011E91)
Detection of state-change in a device
User configurable condition
(PLC#2 connection point)
“DPOS01_EX_CMP”
(512001 8003011E93)
“DPOS01_OEX_BO” §§
(512001 8203011DD3)
Figure 4.8-24 Operate On on the front panel in DPOS01††
†Note: The ILK function can provide the operation criteria for “On”.
‡Note: An “operate condition” signal is generated in the operate-condition logic (see
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If
an alternative “operate-condition” is required, it can be programmed by the user
and used to replace the signal generated by the original operate-condition logic.
The alternative “operate-condition” can be connected to the above using
connection point #1” user configurable condition”. That is set the [DPOS01-
LGCTRCON] to PLC and use “DPOS01IN_TMP_35”.
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for scheme
switch [DPOS01-LGCFEXOT]. The “Operate comleted” signal can also be issued
from logic programmed by the user in place of the logic shown in Figure 4.8-20.
The user-programmed logic is connected internally to the signal “Operate
completed”, hence this is now generated by the user-programmed logic at
connection point #2 “User configurable condition”. That is, set the scheme switch
[DPOS01-LGCFEXOT] to PLC and use “DPOS01IN_TMP_42”.
*Note: The user can set the type of output signal. When Var is set for scheme switch
[DPOS01-PLSM], the output period of the signal is defined by the setting
[DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.