6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 578 -
detected. The detecting signal is denoted as “Traveling OR in Table 3.6-2.
*4
Note: Criteria “unmatched conditions” are decided when the “Test-bit status” in a
command is not identical to the “IED test status”.
*5
Note: The user needs to program the PLC logic Control hierarchy condition”. The
user is also required to connect the logic condition with the select condition logic
using the connection point LEDR01_CTRL_RIGHT. For more information, see
chapter
Control and monitoring application: Control hierarchy
.
LEDR01_CTRL_RIGHT is provided in Table 3.6-3.
*6
Note: To identify the input point of the LEDR function, see Table 3.6-2.
Table 3.6-2 Input signals for condition logic
Signal Number
Signal Name
Description
M/O
522001 000A011001
S4301_STATE
Command Blocking status ( Off / Blocked)
N/A
5A0001 0008001F41
DCB RCV OR
Double Command Blocking(DCB) is in progress.
N/A
5A0001 0008001F40
Traveling OR
Travelling events are detected.
N/A
5A0101 3100001F43
SERI_ERR
Serious Error detected
N/A
523001 000D001F40
ASEQ_MULTI_SEL
Automatic sequence control is in progress.
N/A
Table 3.6-3 PLC connection point (Input point on select condition logic)
Signal Number
Signal Name
Description
M/O
528001 820701ED50
LEDR01_CTRL_RIGHT
LED Reset control hierarchy
M
Table 3.6-4 Setting of LEDR
Setting Name
Description
Default
Setting item or value
LEDDR1_EN
Activate LED reset control
On
Off / On