DPOS01 function (Function ID: 512001)
DPOS01_OSL_BO_CSF”
(512001_8603011DC6)
Command “Remote-On-Control”
ILK† condition (“ON”) passed
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*)
“Automatic sequence control function (AQEQ)§” in progress
Select command
with ILK† condition
Operate command
with ILK† condition
Select command
without ILK† condition
Operate command
without ILK† condition
To “Wait for a next
command”
Figure 4.8-2 Select ‘On’ from the remote-end in DPOS01
††
†Note: The software interlocking (ILK) function provides the operation criteria for “On”.
The ILK function is discussed separately; note that the operation criteria is
defined by the ILK function itself (i.e., the user cannot set the condition).
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPOS01 operation is blocked for the ASEQ function being
in operation. For more information of the ASEQ function, see Chapter
Control and
monitoring application: Automatic sequence control function
.
*Note: The DPOS01 function can run in either the “SBO mode” or the “DIR mode” using
a signal called “ctlmodel” when communication is implemented using IEC61850.
To use this signal, the user must map it for IEC61850 communication.
††
Note: To identify the input and output points of the other DPOS logics, see Table 4.8-5
and Table 4.8-9.