6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 951 -
switch [TPOS01-LGP3EXOT].
TPOS01 function (Function ID: 513001)
Assign to BOs
Operate Cmd.
with ILK condition
S
R
0.1 50.0 s
[TPOS01-CPW]
Operation Cmd.
without ILK condition
Operate condition
[TPOS01-LGCTRCON]
Fixedlogic
Fixedlogic
[TPOS01-LGP3EXOT]
Command PLC-P3-Controlrequiring ILK check (PLC#3
connection point)
ILK condition (“P3”) passed
TPOS1-P3
TPOS01IN_TMP_29
513001 840401EE58
User configurable condition
(PLC#4 connection point)
TPOS01_P3EC_OK_CSF
(5513001 8004011E80)
&
&
1
&
1
1
&
&
&
TPOS01_P3EX_BO
(513001 8204011DD6) §§
Input
Output
Operate logic in TPOS01
To BO connection
TPOS01_P3EC_OK_CS
(513001 8404011E83)
[TPOS01-PLSM]*
Fix
Var
Operation Failed
[TPOS01-RST]
ASEQ function§ is in progress
ASEQ_MULTI_SEL
TPOS01_P3EC_OK_CSF
(513001 8004011E80)
TPOS01_EX_FFL
(513001 8604011E91) ‡‡
To Wait for a command
&
Detection of state-change in a device
&
TPOS01IN_TMP_38
513001 820401EE5E
User configurable condition
(PLC#2 connection point)
1
&
TPOS01_EX_CMP
(5130018004011E93)
Operation Completed
1.0s- 100.0s
0
t
DEV01_P3_INTERLOCK
513001 800401EE37
Command PLC-P3-Control not requiring ILK check
(PLC#4 connection point)
DEV01_P3_COMMAND
513001 800401EE36
Figure 4.9-43 Operate ‘P3-control’ using the PLC function TPOS01
††
Note: The ILK function can provide the criteria for operation for P3” control.
††
Note: To identify the input and output signals of the other TPOS logics, see Table
4.9-16 for PLC#2, Table 4.9-18 for PLC#4, and Table 4.9-20 for the outputs.
Note: An operate condition signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
“operate-condition” to the logic shown in Figure 4.9-43 using connection point #4
“User configurable condition” That is, set the scheme switch [TPOS01-
LGCTRCON] to PLC and using “TPOS01IN_TMP_29”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set for the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting applied
to [TPOS01-CPW]. When Fix is set, the signal ceases when the 43S switch or an
ES is changed.
‡‡Note: The Operate failed” signal “is issued when a state-change remains undetected
following expiration of the setting applied to timer [TPOS01-RST].