6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1265 -
Table 10.2-60 Detailed information in Hexadecimal in CHK_ PLC_DAT
Display
area
Meaning of the detailed information
Left column
Right column
Top
row
00000001 No PLC data exists in the
IED.
00000002 Error in input Data
2
00000004 Error in output Data
3
00000008 Time over in computation
4
00000010 PLC stopped by the editor
5
00010000 Watch dog error
00020000 CPU load exceeded
00040000 File error
00080000 Divided by zero
00100000 Array index out of range
00200000 Stack over flow
00400000 System error
00800000 Working memory over flow
01000000 Internal error
00000001 Watch dog error
00000002 CPU load exceeded
00000003 File error
00000004 Test info string error
00000010 PLC stopped
00000011 No PLC stop Identifier
00000012 Output string is too short
00000013 Input string is too short
00000014 Invalid input parameter
00000015 2nd is of the output string
00000016 Invalid string comparison
00000017 Unsupported type in conversion
00000018 Error in the format string
00000019 Invalid input for format string
0000001A Error during string conversion
0000001B Mismatch in Flash memory
000003E8 Division by zero
000003E9 Array index out of range
000003EA Stack over flow
000003EB System error
000003EC Working memory over flow
Middle
row
(No information)
(No information)
Bottom
row
(No information)
(No information)
2
It can be displayed when Data IDs are selected erroneously in DIN function.
3
It can be displayed when Data IDs are selected erroneously in DOUT function.
4
The kind of tasks (Main_1, Main_2, or Main_3) may be too large.
5
The PLC stops manually by the PLC editor.