The Z1S element generates a trip signal for the trip function (TRC) immediately when
the instantaneous mode is selected using the scheme switch [Z1CNT_INSTOP]. Note that the
scheme switch [LES_EN] can be used to block the Z1S element. The scheme switches [Z1S-
PSBBLK] and [Z1G-PSBBLK] can be used to block CB tripping when a power swing occurs in
the system. The scheme switch [Z1S-MSDET] is also used to cancel the operation condition,
which we have discussed with regard to the selection of the operation of ZS effected by the
occurrences of multi-phase fault or earth-fault. (see section 2.10.3(ii)-3).
The ZS elements generate trip signals if On is set for all of the scheme switches termed
“EN” with zone names [Z*S-EN]. The user should set Off for scheme switch [Z*S-EN] to disable
for issuing the trip signals. Using PLC signal ‘Z*S_ARCBLOCK’, the Z*S elements can issue
‘ARC-BLOCK’ signals for the ARC function via the TRC function; we shall see it later in
Chapter
Relay application: Autoreclose
.
Z1S-OPT
Z1XS-OPT
Z2S-OPT
Z3S-OPT
Z4S-OPT
Z5S-OPT
Z1S-ARC-BLOCK
Z1XS-ARC-BLOCK
Z2S-ARC-BLOCK
Z3S-ARC-BLOCK
Z4S-ARC-BLOCK
Z5S-ARC-BLOCK
Figure 2.10-43 ZS grouping logic for TRC/Recording functions