6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1637 -
INF
Semantics
Contents
GI
Type
ID
COT
Function
Function
ID
Element ID
Name
73
Fault location
X in ohms
Fault location
determined (the
condition of sending
events are the same as
the FMR)
NA
4
1
Carried out by Time tagged measurand function
74
Fault forward/
line
Fault occurred in the
forward direction
NA
2
1
Not supported
75
Fault reverse/
busbar
Fault occurred in the
reverse direction
NA
2
1
Not supported
76
Tele-
protection
Signal
transmitted
Sending a carrier signal
NA
2
1
No default setting
77
Tele-
protection
Signal
received
Reception of a carrier
signal
NA
2
1
No default setting
78
Zone1
Zone1 trip
NA
2
1
No default setting
79
Zone2
Zone2 trip
NA
2
1
No default setting
80
Zone3
Zone3 trip
NA
2
1
No default setting
81
Zone4
Zone4 trip
NA
2
1
No default setting
82
Zone5
Zone5 trip
NA
2
1
No default setting
83
Zone6
Zone6 trip
NA
2
1
Not supported
84
General
start/pick-up
The OR signal
generated by operated
relays
OK
2
1,9
No default setting
85
Breaker
failure
CBF relay trip
NA
2
1
CBF
453001
8B00011B27
CBF1_TRIP
86
Trip
measuring
system L1
NA
2
1
Not supported
87
Trip
measuring
system L2
NA
2
1
Not supported
88
Trip
measuring
system L3
NA
2
1
Not supported
89
Trip
measuring
system E
NA
2
1
Not supported
90
Trip I>
OC trip in the IDMT
mode
NA
2
1
No default setting
91
Trip I>>
OC trip in the DT mode
NA
2
1
No default setting
92
Trip IN>
EF trip in the IDMT
mode
NA
2
1
No default setting
93
Trip IN>>
EF trip in the DT mode
NA
2
1
No default setting
128
CB ‘on’ by AR
NA
1
1
ARC
4A6001
8000011B6C
ARC1 CLOSE
COMMAND
129
CB ‘on’ by
long-time AR
NA
1
1
Not supported
130
AR blocked
OK
1
1, 9
ARC
4A6001
8200001BB4
ARC_BLOCK